Skip to main content
FE to PEPrep

Free PE Mech — HVAC practice problems

Ten real questions from our PE Mechanical: HVAC and Refrigeration bank, drawn from 10 of its 14 study topics, with fully worked solutions and the same figures our members get. No signup, no email. Try each one first, then reveal the solution.

4 with figures10 topicsFull worked solutions
  1. 1
    medium
    A. Sensible & total energy recovery
    At a site 5,000 ft5{,}000\,\text{ft} above sea level, a sensible recovery wheel preheats the outdoor air for an office air handler. The wheel handles 4,000 cfm4{,}000\,\text{cfm} of outdoor air entering at 20 °F20\,°\text{F} and an equal 4,000 cfm4{,}000\,\text{cfm} of exhaust air entering at 72 °F72\,°\text{F} (both airflows at site conditions), and its sensible effectiveness at this balanced flow is 70%70\%. The recovered sensible heat rate (Btu/h) is most nearly:
    Air-to-air energy recovery: separate supply (OA→SA) and exhaust (RA→EA) airstreams through a recovery wheel4,000 cfm each · ε = 0.7OA 20°FSARA 72°FEA

    Figure — drag or pinch to move around

    1. 57,400 Btu/h
    2. 134,000 Btu/h
    3. 160,000 Btu/h
    4. 185,000 Btu/h
    Show the answer & worked solution

    Answer: B.134,000 Btu/h

    With balanced flow the maximum sensible transfer uses the span between the two entering streams (§9.2.7, p. 483): t3−t1=72−20=52 °Ft_3-t_1=72-20=52\,°\text{F}. At 5,0005{,}000 ft the standard-air sensible factor is Cs=0.92C_s=0.92 (§9.1.7, p. 454; §9.1.8, p. 456), applied directly to the site airflow, so qs,max=Cs Q (t3−t1)=0.92(4,000)(52)=191,360q_{s,max}=C_s\,Q\,(t_3-t_1)=0.92(4{,}000)(52)=191{,}360 Btu/h and qs=εs qs,max=0.7×191,360=133,952q_s=\varepsilon_s\,q_{s,max}=0.7\times191{,}360=133{,}952 Btu/h. Distractors: used the sea-level sensible factor 1.101.10 at 5,0005{,}000 ft (160,000160{,}000); applied εs\varepsilon_s to the exhaust temperature alone, 0.7×72 °F0.7\times72\,°\text{F}, dropping the outdoor-air temperature from the span (185,000185{,}000); and applied 1−εs=0.31-\varepsilon_s=0.3, the share not recovered (57,40057{,}400).
  2. 2
    medium
    A. LMTD, effectiveness-NTU & coil duty
    In a heat-recovery plate heat exchanger, 40 gpm40\,\text{gpm} of process water is cooled from 140140°F to 6565°F by 75 gpm75\,\text{gpm} of domestic water entering at 5050°F. The two streams flow in counterflow, both are water, and the overall heat-transfer coefficient is U=500 Btu/(hr-ft2-°F)U=500\,\text{Btu/(hr-ft}^2\text{-°F)}. The required heat-transfer area is most nearly:
    Counterflow heat exchanger: hot stream in at 140 °F and out at 65 °F; cold stream in at 50 °F, outlet temperature unknownhotcoldTHi = 140 °FTHo = 65 °FTCi = 50 °FTCo = ?counterflow heat exchanger

    Figure — drag or pinch to move around

    1. 60 ft²
    2. 92.3 ft²
    3. 103 ft²
    4. 200 ft²
    Show the answer & worked solution

    Answer: C.103 ft²

    Duty from the process water (§9.1.7, standard water): Q˙=500 (40)(140−65)=1,500,000\dot Q=500\,(40)(140-65)=1{,}500{,}000 Btu/hr. The domestic water absorbs the same duty, so TCo=TCi+Q˙500 (75)=50+40=90T_{Co}=T_{Ci}+\dfrac{\dot Q}{500\,(75)}=50+40=90°F. Counterflow terminal differences (§5.5.3): THi−TCo=140−90=50T_{Hi}-T_{Co}=140-90=50°F and THo−TCi=65−50=15T_{Ho}-T_{Ci}=65-50=15°F, so ΔTlm=50−15ln⁡(50/15)=29.07\Delta T_{lm}=\dfrac{50-15}{\ln(50/15)}=29.07°F. With F=1F=1 for counterflow (§5.5.1), A=Q˙UF ΔTlm=1,500,000500 (1)(29.07)=103A=\dfrac{\dot Q}{U F\,\Delta T_{lm}}=\dfrac{1{,}500{,}000}{500\,(1)(29.07)}=103 ft². Distractors: used the ARITHMETIC mean of the terminal differences, (50+15)/2=32.5(50+15)/2=32.5°F, in place of the log-mean (92.392.3 ft²); assumed the domestic water warms as much as the process water cools, TCo=50+75=125T_{Co}=50+75=125°F, ignoring the different flows, which leaves 1515°F at both ends (200200 ft²); and used the LARGER terminal difference, 5050°F, as the driving difference (6060 ft²).
  3. 3
    medium
    A. Load components & supply airflow
    An office AHU cooling a perimeter zone at a sea-level site must offset a total room cooling load of 75,000 Btu/h75{,}000\,\text{Btu/h} with a sensible heat ratio of 0.800.80. The room is held at 75 °F75\,°\text{F}, and the supply air enters the room at 55 °F55\,°\text{F} (see the AHU schematic). The required supply-air flow (cfm) is most nearly:
    Air-handling unit: outdoor and return air mix, then filter, cooling coil and supply fanOARAMAfiltercooling coilfanSA

    Figure — drag or pinch to move around

    1. 833 cfm
    2. 2730 cfm
    3. 3410 cfm
    4. 4340 cfm
    Show the answer & worked solution

    Answer: B.2730 cfm

    The supply air is sized on the room SENSIBLE load; the latent part is removed at the coil. With SHR == sensible/total (§7.1), qs=SHR qt=0.80(75,000)=60,000q_s=\text{SHR}\,q_t=0.80(75{,}000)=60{,}000 Btu/h. Δt=troom−tsupply=75−55=20 °F\Delta t=t_{room}-t_{supply}=75-55=20\,°\text{F}, and the §9.1.7 sea-level sensible relation qs=1.10 Q Δtq_s=1.10\,Q\,\Delta t gives Q=qs1.10 Δt=60,0001.10(20)=2,727Q=\dfrac{q_s}{1.10\,\Delta t}=\dfrac{60{,}000}{1.10(20)}=2{,}727 cfm. Distractors: paired the total load with the total-heat factor 4.54.5 but a temperature difference; 4.54.5 multiplies an enthalpy difference (833833); sized the air on the TOTAL load, 75,000/[1.10(20)]75{,}000/[1.10(20)], though the latent part is removed at the coil and does not set the airflow (3,4093{,}409); and divided by the latent factor per grain, 4840/7000=0.6914840/7000=0.691, instead of the sensible 1.101.10 (4,3394{,}339).
  4. 4
    medium
    A. Vapor-compression cycle, COP & capacity
    A food-plant cold room is served by an open-drive compressor operating the R-134a cycle shown (states 1→2→3→4), with h1=104h_1=104, h2=119h_2=119, h3=41.6h_3=41.6, and h4=41.6 Btu/lbh_4=41.6\,\text{Btu/lb}. The compressor's electric motor has an efficiency of 0.900.90. The cooling coefficient of performance based on the electrical input to the motor is most nearly:
    R-134a vapor-compression cycle on a pressure–enthalpy (p–h) diagram; the saturation dome is drawn from R-134a property datap (psia, log scale)pcpecrit.R-134a1234h3=h4=41.6h1=104h2=119h (Btu/lb)

    Figure — drag or pinch to move around

    1. 3.74
    2. 4.16
    3. 6.24
    4. 12.8
    Show the answer & worked solution

    Answer: A.3.74

    From the diagram's enthalpies (§4.5.2), the cycle COP is COPref=h1−h4h2−h1=104−41.6119−104=62.415=4.16\text{COP}_{ref}=\dfrac{h_1-h_4}{h_2-h_1}=\dfrac{104-41.6}{119-104}=\dfrac{62.4}{15}=4.16, cooling per unit of SHAFT work. The motor needs Wel=Wshaft/ηmW_{el}=W_{shaft}/\eta_m (§1.11.1), so on the electrical input COPel=COPref ηm=4.16(0.90)=3.74\text{COP}_{el}=\text{COP}_{ref}\,\eta_m=4.16(0.90)=3.74. With an open drive the motor loss leaves as heat to the machine room and never reaches the refrigerant, so h2h_2 is unchanged. Distractors: stopped at the cycle COP, 4.164.16, leaving out the motor loss that the electrical input has to cover; left h4h_4 out of the numerator, h1h2−h1 ηm=6.24\dfrac{h_1}{h_2-h_1}\,\eta_m=6.24; and multiplied the electrical COP by 3.4123.412 Btu/h per W, 12.7712.77, which turns a COP into an EER (§9.6.2), not a dimensionless COP.
  5. 5
    hard
    A. Cooling-tower range, approach & water balance
    A water-cooled chiller serving an office building carries 300 tons300\,\text{tons} of refrigeration at a full-load efficiency of 0.60 kW/ton0.60\,\text{kW/ton}. Its cooling tower sends condenser water to the chiller at 85 °F85\,°\text{F} and receives it back at 95 °F95\,°\text{F}, with a design wet-bulb of 78 °F78\,°\text{F}. The condenser-water flow (gpm) is most nearly:
    1. 720 gpm
    2. 843 gpm
    3. 900 gpm
    4. 1,200 gpm
    Show the answer & worked solution

    Answer: B.843 gpm

    The tower rejects the refrigeration effect plus the compressor input. Compressor input =300×0.60=180 kW=300\times0.60=180\,\text{kW}, so Qo=300(12,000)+180(3,412)=3,600,000+614,160=4,214,160Q_o=300(12{,}000)+180(3{,}412)=3{,}600{,}000+614{,}160=4{,}214{,}160 Btu/h (1 ton =12,000=12{,}000 Btu/h and 1 W =3.412=3.412 Btu/h, §1.1). Range =95−85=10 °F=95-85=10\,°\text{F}, and from Qo=500 (gpm)(Tent−Tlvg)Q_o=500\,(\text{gpm})(T_{ent}-T_{lvg}) (§9.3.9.2), gpm=4,214,160500×10=843\text{gpm}=\dfrac{4{,}214{,}160}{500\times10}=843 gpm (≈ 2.812.81 gpm/ton). Distractors: used the refrigeration load alone, 300×12,000300\times12{,}000 Btu/h, leaving out the compressor heat the tower also rejects, 720720 gpm; used the 3 gpm/ton rule of thumb, which rests on the 15,00015{,}000 Btu/h cooling-tower ton (0.880.88 kW/ton) and a 10 °F10\,°\text{F} range, 900900 gpm; and used the approach, 85−78=7 °F85-78=7\,°\text{F}, as the water Δt\Delta t instead of the range, 1,2001{,}200 gpm.
  6. 6
    medium
    A. Duct sizing, friction & fan pressure
    A supply trunk run has 150 ft150\,\text{ft} of straight duct sized for a friction rate of 0.08 in. w.g. per 100 ft0.08\,\text{in. w.g. per }100\text{ ft}, plus fittings whose loss coefficients sum to ΣC=2.2\Sigma C=2.2, all referenced to the duct velocity of 1,100 ft/min1{,}100\,\text{ft/min}. For standard air, the total pressure loss of the run (in. w.g.) is most nearly:
    1. 0.12 in. w.g.
    2. 0.195 in. w.g.
    3. 0.246 in. w.g.
    4. 0.286 in. w.g.
    Show the answer & worked solution

    Answer: D.0.286 in. w.g.

    Straight duct: 0.08×150100=0.120.08\times\dfrac{150}{100}=0.12 in. w.g. Velocity pressure (§9.3.6.1): pv=(1,100/4,005)2=0.0754p_v=(1{,}100/4{,}005)^2=0.0754 in. w.g., so the fittings lose ΣC pv=2.2×0.0754=0.166\Sigma C\,p_v=2.2\times0.0754=0.166 in. w.g. (§9.3.6.4). Section total (§9.3.6.6): 0.12+0.166=0.2860.12+0.166=0.286 in. w.g. Distractors: left out the fittings, reporting the straight-duct friction alone (0.120.12); took the friction rate itself as the straight-duct loss, ignoring the 150150-ft length (0.08+0.166=0.2460.08+0.166=0.246); and added one velocity pressure for the fittings instead of ΣC⋅pv\Sigma C\cdot p_v (0.12+0.0754=0.19540.12+0.0754=0.1954).
  7. 7
    medium
    A. Combustion, boiler/furnace efficiency & fuel rate
    A packaged boiler in a school heating plant fires 12 gal/h12\,\text{gal/h} of No. 2 fuel oil, and the combustion air supplied to its burner is measured at 1,590 lb/h1{,}590\,\text{lb/h}. The percent excess air is most nearly:
    1. 18.3 %
    2. 20 %
    3. 25 %
    4. 28.6 %
    Show the answer & worked solution

    Answer: C.25 %

    The §10.3 table of approximate air requirements (p. 549) gives 106106 lb of air per gallon for No. 2 fuel oil, so the theoretical air is 106×12=1,272106\times12=1{,}272 lb/h. Percent excess air (§10.2, p. 548; §10.5.1, p. 553) =air supplied−theoretical airtheoretical air×100=1,590−1,2721,272×100=25%=\dfrac{\text{air supplied}-\text{theoretical air}}{\text{theoretical air}}\times100=\dfrac{1{,}590-1{,}272}{1{,}272}\times100=25\%. Distractors: read the No. 1 fuel oil row of the table (103103 lb of air per gallon) instead of the No. 2 fuel oil row, so the theoretical air came out 1,2361{,}236 lb/h (28.6%28.6\%); read the No. 5 fuel oil row of the table (112112 lb of air per gallon) instead of the No. 2 fuel oil row, so the theoretical air came out 1,3441{,}344 lb/h (18.3%18.3\%); and divided the excess air by the air supplied instead of the theoretical air, 318/1,590×100=20%318/1{,}590\times100=20\%.
  8. 8
    medium
    A. Valve/damper sizing, sensors & control response
    A two-way control valve is being selected for an office air handler's chilled-water coil. At the design flow of 60 gpm60\,\text{gpm} the coil's water-side pressure drop is 12 ft12\,\text{ft} of water, and the branch piping, fittings and balancing valve add another 4 ft4\,\text{ft} of water. The valve is to have an authority of 50%50\% at design flow. The required valve flow coefficient CvC_v is most nearly:
    1. 15 (gpm/√psi)
    2. 22.8 (gpm/√psi)
    3. 26.3 (gpm/√psi)
    4. 32.2 (gpm/√psi)
    Show the answer & worked solution

    Answer: B.22.8 (gpm/√psi)

    Authority (§11.3.2, p. 559) is the open-valve drop over the total branch drop, valve included: β=ΔpvalveΔpvalve+Δpcoil+piping\beta=\dfrac{\Delta p_{valve}}{\Delta p_{valve}+\Delta p_{coil+piping}}, so Δpvalve=β1−β Δpcoil+piping\Delta p_{valve}=\dfrac{\beta}{1-\beta}\,\Delta p_{coil+piping}. The coil and piping drop 12+4=1612+4=16 ft of water =16/2.31=6.93=16/2.31=6.93 psi, so Δpvalve=0.50.5×6.93=6.93\Delta p_{valve}=\dfrac{0.5}{0.5}\times6.93=6.93 psi. Then (§11.3.8, p. 560; water, so no specific-gravity correction) Cv=QΔp=606.93=22.8C_v=\dfrac{Q}{\sqrt{\Delta p}}=\dfrac{60}{\sqrt{6.93}}=22.8. Distractors: used the feet of water as if they were psi, Δpvalve=16\Delta p_{valve}=16 (Cv=15C_v=15); took the authority against the coil and piping alone, Δpvalve=0.5×6.93=3.46\Delta p_{valve}=0.5\times6.93=3.46 psi, leaving the valve out of the total (Cv=32.2C_v=32.2); and counted only the coil's 1212 ft and dropped the piping, fittings and balancing valve from the branch (Δpvalve=5.19\Delta p_{valve}=5.19 psi, Cv=26.3C_v=26.3).
  9. 9
    medium
    A. Chillers, heat pumps & thermal storage
    During a field performance test, a water-cooled centrifugal chiller cools 420 gpm420\,\text{gpm} of chilled water from 58 °F58\,°\text{F} to 44 °F44\,°\text{F} while drawing 150 kW150\,\text{kW} of electric power. Its coefficient of performance for cooling is most nearly:
    1. 4.1
    2. 5.74
    3. 6.74
    4. 19.6
    Show the answer & worked solution

    Answer: B.5.74

    Cooling delivered (§9.1.7, p. 455): q=500 Qw Δt=500(420)(58−44)=2,940,000q=500\,Q_w\,\Delta t=500(420)(58-44)=2{,}940{,}000 Btu/h. Electric input in the same units (11 W =3.412=3.412 Btu/h, §1.1, p. 2): W=150 kW×3,412 Btu/h per kW=511,800W=150\,\text{kW}\times3{,}412\,\text{Btu/h per kW}=511{,}800 Btu/h. COP for cooling (§4.5.1, p. 290): COP=QLW=2,940,000511,800=5.74\text{COP}=\dfrac{Q_L}{W}=\dfrac{2{,}940{,}000}{511{,}800}=5.74. Distractors: took the load from the 2.4-gpm-per-ton rule of thumb, which assumes a 10 °F10\,°\text{F} range, instead of the measured 14 °F14\,°\text{F} (420/2.4=175420/2.4=175 tons, COP 4.14.1); reported the heat-pump COP, adding the work to the heat removed, (QL+W)/W=6.74(Q_L+W)/W=6.74; and divided Btu/h by watts without the 3.4123.412 Btu/h-per-watt factor, 2,940,000/150,000=19.62{,}940{,}000/150{,}000=19.6, which is the EER, not the COP.
  10. 10
    medium
    A. Hydronic flow, head loss, steam & expansion
    An office air handler's chilled-water coil cools 22,000 cfm22{,}000\,\text{cfm} of standard air from 80 °F80\,°\text{F} dry bulb with an enthalpy of 31.5 Btu/lb31.5\,\text{Btu/lb} dry air to 55 °F55\,°\text{F} dry bulb with an enthalpy of 22.6 Btu/lb22.6\,\text{Btu/lb} dry air. Chilled water is supplied at 44 °F44\,°\text{F} and returns at 58 °F58\,°\text{F}. The required chilled-water flow (gpm) is most nearly:
    1. 86.4 gpm
    2. 126 gpm
    3. 160 gpm
    4. 176 gpm
    Show the answer & worked solution

    Answer: B.126 gpm

    The coil both cools and dehumidifies, so the water carries the total load, which the air's enthalpy change captures. Air side (§9.1.7, p. 454): qt=4.5 Qs Δh=4.5(22,000)(31.5−22.6)=881,100q_t=4.5\,Q_s\,\Delta h=4.5(22{,}000)(31.5-22.6)=881{,}100 Btu/h. Water side (§9.1.7, p. 455), with the water's own rise Δt=58−44=14 °F\Delta t=58-44=14\,°\text{F}: Qw=qw500 Δt=881,100500(14)=126Q_w=\dfrac{q_w}{500\,\Delta t}=\dfrac{881{,}100}{500(14)}=126 gpm. Distractors: sized the water for the sensible load only, 1.10(22,000)(80−55)=605,0001.10(22{,}000)(80-55)=605{,}000 Btu/h, missing the latent heat of the moisture the coil condenses (86.486.4 gpm); used the leaving-air to supply-water difference (11 °F11\,°\text{F}) as the water Δt\Delta t (160160 gpm); and applied the 2.4-gpm-per-ton rule of thumb, which assumes a 10 °F10\,°\text{F} rise, to the 73.473.4-ton load instead of the actual 14 °F14\,°\text{F} (176176 gpm).

That was ten. There are 1,400+ more.

The full PE Mechanical: HVAC and Refrigeration bank covers every knowledge area, with full-length timed mock exams at the real exam's 80 questions and time limit, and an AI tutor to talk any problem through.

Studying for a different exam? See free practice problems for all 11 exams, or read our FE & PE study guides.

These ten are among the free sample questions anyone can practice in the app, no account needed. The paid bank is separate. Independent study resource; not affiliated with, endorsed by, or sponsored by NCEES.