Free PE Mech — HVAC practice problems
Ten real questions from our PE Mechanical: HVAC and Refrigeration bank — one from each knowledge area, with the same exam-realistic figures and fully worked solutions our members get. No signup, no email. Try each one first, then reveal the solution.
- 1mediumA. Sensible & total energy recoveryA sensible recovery wheel preheating the outdoor air for an office AHU draws of outdoor air at and preheats it to leaving the recovery device. Using , the recovered SENSIBLE heat rate is most nearly:
- 114000 Btu/h
- 181000 Btu/h
- 185000 Btu/h
- 756000 Btu/h
Show the answer & worked solution
Answer: B.181000 Btu/h
; Btu/h. Distractors: used the LATENT coefficient in place of the sensible (); used the TOTAL-enthalpy coefficient as if were a in Btu/lb (); and used instead of (). - 2mediumA. Load components & supply airflowAn office AHU cooling a perimeter zone must offset a room SENSIBLE load of . The room is held at and the coil delivers supply air at (see the AHU schematic). Using , the required supply-air flow is most nearly:
- 667 cfm
- 3240 cfm
- 4410 cfm
- 2780 cfm
Show the answer & worked solution
Answer: D.2780 cfm
; cfm. Distractors: used the LATENT coefficient in place of the sensible (); used the total-enthalpy coefficient (); and MULTIPLIED by instead of dividing (). - 3easyA. LMTD, effectiveness-NTU & coil dutyA chilled-water cooling coil runs in pure COUNTERFLOW. The hot stream enters at °F and leaves at °F; the cold stream enters at °F and leaves at °F. The log-mean temperature difference is most nearly:
- 40 °F
- 34.1 °F
- 50 °F
- 39.2 °F
Show the answer & worked solution
Answer: D.39.2 °F
Counterflow terminal differences: °F and °F. °F. Distractors: used the ARITHMETIC mean °F (always larger than the log-mean); paired the ends as in PARALLEL flow, and (°F); and took the LARGER terminal difference °F alone (no averaging). - 4easyA. Vapor-compression cycle, COP & capacityA walk-in cooler operates the R-134a cycle shown (states 1→2→3→4) with , , , and . The coefficient of performance for cooling is most nearly:
- 0.806
- 5.16
- 4.16
- 0.24
Show the answer & worked solution
Answer: C.4.16
. Distractors: SWAPPED numerator and denominator, (work over effect); used the heating-COP form with the full drop in the numerator, (one greater than the cooling COP); and divided the effect by the condenser REJECTION instead of the work, . - 5hardA. Cooling-tower range, approach & water balanceA water-cooled chiller serving an office chiller plant carries of cooling. The condenser rejects about (refrigeration plus compressor work) to a tower run at a range. Using , the condenser-water flow required is most nearly:
- 417000 gpm
- 900 gpm
- 720 gpm
- 7500 gpm
Show the answer & worked solution
Answer: B.900 gpm
Heat rejection Btu/h; (≈ gpm/ton). Distractors: used Btu/h per ton (cooling only, omitted the compressor work, gpm); used instead of in — i.e. dropped the water factor ( gpm); and used the AIR coefficient instead of for water (). - 6mediumA. Economics & electrical for HVACA 460-V chiller compressor motor draws a line current of 95 A at a line-to-line voltage of 460 V with a power factor of 0.88. The real (true) electrical power it draws is most nearly:
- 115 kW
- 38.5 kW
- 75.7 kW
- 66.6 kW
Show the answer & worked solution
Answer: D.66.6 kW
kW. Distractors: dropped the (used the single-phase form ); dropped the power factor, giving the apparent power kVA (not real kW); and used instead of , (over by ). - 7easyA. Duct sizing, friction & fan pressureA supply trunk run is long and is sized for a friction rate of . The straight-duct friction loss over the run is most nearly:
- 0.12 in. w.g.
- 12 in. w.g.
- 0.08 in. w.g.
- 0.012 in. w.g.
Show the answer & worked solution
Answer: A.0.12 in. w.g.
in. w.g. Distractors: multiplied by the full length, forgetting the friction rate is per 100 ft (, high); divided by instead of (); and reported the friction RATE itself (ignored the run length). - 8easyA. Combustion, boiler/furnace efficiency & fuel rateOn a natural-gas boiler, a tune-up technician measures an actual air–fuel ratio of against the stoichiometric value . The percent excess air is most nearly:
- 2.94 %
- 20 %
- 83.3 %
- 120 %
Show the answer & worked solution
Answer: B.20 %
Percent theoretical air , so percent EXCESS air . Distractors: reported the percent THEORETICAL air (forgot to subtract the ); INVERTED the ratio to ; and used the absolute AFR DIFFERENCE as if it were already a percentage. - 9easyA. Valve/damper sizing, sensors & control responseA chilled-water terminal control valve passes of water with a pressure drop of across the valve. The required valve flow coefficient is most nearly:
- 3.16 (gpm/psi0.5)
- 20 (gpm/psi0.5)
- 10 (gpm/psi0.5)
- 80 (gpm/psi0.5)
Show the answer & worked solution
Answer: B.20 (gpm/psi0.5)
. Distractors: divided by itself instead of (); MULTIPLIED by instead of dividing (); and square-rooted the flow as well, (). - 10easyA. Chillers, heat pumps & thermal storageA performance test rates a water-cooled centrifugal chiller at 0.56 kW/ton at full load (1 ton of cooling = 3.516 kW). Its coefficient of performance for cooling is most nearly:
- 1.97
- 6.28
- 1.79
- 21.4
Show the answer & worked solution
Answer: B.6.28
. Distractors: MULTIPLIED by the kW/ton instead of dividing, ; computed the EER and mislabeled it COP (off by the Btu/Wh factor); and dropped the , using .
That was ten. There are thousands.
The full PE Mechanical: HVAC and Refrigeration bank covers every knowledge area at this depth, with timed mock exams that mirror the real 80-question paper and an AI tutor grounded in the NCEES PE Mechanical Reference Handbook — so it can't confidently feed you a wrong answer.
Studying for a different exam? See free practice problems for all 11 exams, or read our FE & PE study guides.
These are the same free sample questions available to anyone with an account — the paid bank is separate. Independent study resource; not affiliated with, endorsed by, or sponsored by NCEES.