Skip to main content
FE to PEPrep

Free PE Power practice problems

Ten real questions from our PE Electrical and Computer: Power bank, drawn from all 9 of its study topics, with fully worked solutions and the same figures our members get. No signup, no email. Try each one first, then reveal the solution.

10 with figures9 topicsFull worked solutions
  1. 1
    medium
    A. Three-phase circuits
    A three-phase induction motor delivers 50 hp at full load. At this load its efficiency is 91% and its power factor is 0.86 lagging. The motor is supplied at 480 V (line-to-line). The full-load line current is most nearly:
    Three-phase induction motor fed by three line conductors A, B and C, with the line-to-line voltage marked between lines A and B and the line current on line A3-phase supplyABCMVLL = 480 VIL50 hpη = 91%pf = 0.86 lag

    Figure — drag or pinch to move around

    1. 44.9 A
    2. 49.3 A
    3. 52.2 A
    4. 57.3 A
    Show the answer & worked solution

    Answer: D.57.3 A

    Shaft output: Pout=50×746 W=37.3P_{out}=50\times746\text{ W}=37.3 kW. Electrical input: Pin=Pout/η=37.3/0.91=40.99P_{in}=P_{out}/\eta=37.3/0.91=40.99 kW. The handbook's induction-motor power flow (§4.2.5) gives Pin=3 VTILcos⁡θP_{in}=\sqrt3\,V_TI_L\cos\theta, so IL=40.99×1033(480)(0.86)=57.3I_L=\dfrac{40.99\times10^3}{\sqrt3(480)(0.86)}=57.3 A. Distractors: 52.2 A leaves out the efficiency, taking the shaft output as the electrical input; 49.3 A leaves out the power factor, treating the input kW as kVA; and 44.9 A divides the shaft output by 3 VT\sqrt3\,V_T with neither the efficiency nor the power factor.
  2. 2
    medium
    E. Testing
    A transformer turns-ratio (TTR) test set is connected to a single-phase transformer rated 13800–480 V. The HV winding has four 2.5% taps, two above and two below rated voltage, and the de-energized tap changer is on the second tap above rated voltage. The set measures a ratio of 30.11. The acceptance criterion (IEEE C57.152) is ±0.5% of the voltage ratio the nameplate lists for the tap in use. The ratio error and the test result are most nearly:
    Figure for this questionTTR test set13800:480 Vunder testX1–X2

    Figure — drag or pinch to move around

    1. -0.26% — pass
    2. -0.08% — pass
    3. +4.73% — fail (outside ±0.5%)
    4. +10.24% — fail (outside ±0.5%)
    Show the answer & worked solution

    Answer: A.-0.26% — pass

    The turns ratio is the no-load voltage ratio, a=N1/N2=E1/E2a=N_1/N_2=E_1/E_2 (§4.3.1.1), so the reference is the nameplate ratio for the tap in service. The tap changer is on the second tap above rated voltage, 2 × 2.5% = 5% above, which sets the HV winding for 1.05×13800=144901.05\times13800=14490 V, so a=14490/480=30.188a=14490/480=30.188. Error =30.11−30.18830.188×100=−0.26%=\dfrac{30.11-30.188}{30.188}\times100=-0.26\%, which is inside the ±0.5% band, so the unit passes; the sign says the measured ratio is low. Distractors: compared with the rated-tap ratio 13800/480=28.7513800/480=28.75, ignoring the tap in service (+4.73%); applied the tap the wrong way, 0.95×138000.95\times13800 on the HV side (+10.24%); and reported the raw ratio difference 30.11−30.18830.11-30.188 as if it were already a percent (-0.08%).
  3. 3
    medium
    C. Special occupancies and systems
    A hospital's Type 1 essential electrical system has a life safety branch and a critical branch, both restored automatically within 10 seconds of a loss of normal power, and an equipment branch on delayed-automatic or manual connection; loads outside those branches stay on the normal system. Per the NEC, to which portion of the system should the corridor egress illumination and exit signs in an inpatient nursing unit be connected?
    Hospital Type 1 essential electrical system: the normal source and the generator each feed three transfer switches, one per branch (life safety, critical, equipment), and the normal source also feeds the nonessential loadsNormal sourceserviceNonessentialloadsGGenerator (alternate source)ATSNELife safety≤ 10 sATSNECritical≤ 10 sATSNEEquipmentdelayed-automaticor manual

    Figure — drag or pinch to move around

    1. Nonessential (normal system) loads
    2. Critical branch
    3. Equipment branch
    4. Life safety branch
    Show the answer & worked solution

    Answer: D.Life safety branch

    This load belongs on the life safety branch: the life safety branch (517.33) carries only life-safety functions (illumination of the means of egress, exit signs, alarm and alerting systems, emergency communications) and is restored automatically within 10 seconds. Being in a patient-care unit does not move them to the critical branch: the critical branch's lighting is task illumination serving patient care (517.34), while illumination of the means of egress and exit signs are life-safety functions (517.33) wherever the corridor runs. The other choices misplace it: the critical branch (517.34) carries task illumination, fixed equipment, selected receptacles and special power circuits serving patient care, and nurse call, and is restored automatically within 10 seconds; the equipment branch (517.35) carries the listed mechanical loads (medical suction and air, smoke control, kitchen hood systems, sump pumps, ventilation and heating for patient areas) on delayed-automatic or manual connection; the normal system carries every load that no branch list names, and those loads may stay de-energized on loss of normal power. None of those scopes covers this load.
  4. 4
    medium
    B. Surge protection
    A metal-oxide surge arrester is being selected for a 13.2 kV (line-to-line), solidly grounded, four-wire multigrounded-neutral distribution system that may operate continuously at 105% of nominal voltage. Standard arrester MCOV values are 2.55, 5.1, 7.65, 8.4, 10.2, 12.7, 15.3, 19.5, 22, and 24.4 kV. The minimum standard MCOV suitable for this application is:
    Figure for this questionUtility13.2 kVeffectively groundedMOV arresterMCOV = ?transformerload

    Figure — drag or pinch to move around

    1. 7.65 kV
    2. 8.4 kV
    3. 10.2 kV
    4. 15.3 kV
    Show the answer & worked solution

    Answer: B.8.4 kV

    NEC 2020 242.42(A) requires the arrester rating to cover the maximum continuous operating voltage at its point of application, taken phase-to-ground on a solidly grounded system: the arrester is connected line-to-ground, and a ground fault does not hold the healthy phases at line-to-line voltage. That voltage is the line-to-neutral value raised by the continuous allowance, MCOV≥1.05×13.2/3=1.05×7.62=8.00MCOV \ge 1.05\times13.2/\sqrt3 = 1.05\times7.62 = 8.00 kV, and the smallest listed MCOV at or above it is 8.4 kV; a lower rating would conduct continuously and overheat. Distractors: dropped the 105% allowance and sized to the nominal VLN=7.62V_{LN} = 7.62 kV, giving 7.65 kV; used the phase-to-phase basis that applies only to impedance-grounded or ungrounded systems, 1.05×13.2=13.861.05\times13.2 = 13.86 kV, giving 15.3 kV; and applied the 125% factor that 242.42(B) sets for silicon-carbide arresters to this metal-oxide unit, 1.25×8.00=10.001.25\times8.00 = 10.00 kV, giving 10.2 kV.
  5. 5
    medium
    A. Instrument transformers & metering
    A balanced three-phase, three-wire load is measured by the two-wattmeter method. The meters read W1=12W_1=12 kW and W2=4W_2=4 kW. The load power factor is most nearly:
    Figure for this question3-phase sourceABCW1W2Load

    Figure — drag or pinch to move around

    1. 0.536
    2. 0.655
    3. 0.756
    4. 0.894
    Show the answer & worked solution

    Answer: C.0.756

    In the two-wattmeter method on a balanced three-wire load, the sum of the readings is the total real power and 3\sqrt3 times their difference is the total reactive power, so the readings alone fix the power-factor angle. P=W1+W2=16P=W_1+W_2=16 kW and tan⁡θ=3(W1−W2)/(W1+W2)=3(12−4)/16=0.866⇒θ=40.9∘\tan\theta=\sqrt3(W_1-W_2)/(W_1+W_2)=\sqrt3(12-4)/16=0.866\Rightarrow\theta=40.9^\circ, so PF=cos⁡θ=0.756PF=\cos\theta=0.756. The distractors dropped the 3\sqrt3, tan⁡θ=(W1−W2)/(W1+W2)\tan\theta=(W_1-W_2)/(W_1+W_2) (0.894); reported sin⁡θ\sin\theta, the reactive factor, as the power factor (0.655); and added PP and QQ arithmetically for the apparent power, P/(P+Q)P/(P+Q) (0.536).
  6. 6
    medium
    A. Power electronics (converters, inverter-based resources, VFDs)
    A three-phase six-pulse diode bridge rectifier is supplied at 480 V line-to-line. With ideal devices and negligible commutation overlap, the average DC output voltage is most nearly:
    Figure for this questiontvdcvdc (6-pulse)

    Figure — drag or pinch to move around

    1. 648 V
    2. 679 V
    3. 917 V
    4. 1120 V
    Show the answer & worked solution

    Answer: A.648 V

    The handbook's uncontrolled three-phase full-wave bridge (§3.2.2.1) gives V0=3Vm,L−Lπ=0.955 Vm,L−LV_0=\dfrac{3V_{m,L-L}}{\pi}=0.955\,V_{m,L-L}, where Vm,L−LV_{m,L-L} is the PEAK line-to-line voltage. The 480 V rating is rms, so Vm,L−L=2×480=678.8V_{m,L-L}=\sqrt2\times480=678.8 V and V0=0.955×678.8=648V_0=0.955\times678.8=648 V (about 1.35 VLL1.35\,V_{LL}). Distractors: the peak line-to-line voltage 2 VLL\sqrt2\,V_{LL} instead of the average (679 V); the 1.35 rms factor applied to the peak 2 VLL\sqrt2\,V_{LL}, converting twice (917 V); and the line-to-neutral factor 2.34 applied to the line-to-line voltage (1120 V).
  7. 7
    medium
    A. Overcurrent protection
    A 13.8 kV feeder carries a maximum continuous load of 420 A. Its 51 phase time-overcurrent relay is fed from wye-connected 600:5 CTs, and company practice sets the phase pickup at 125%125\% of maximum load. The required relay tap (pickup) setting, in secondary amperes, is most nearly:
    Figure for this question13.8 kV bus600:551feeder420 A max load

    Figure — drag or pinch to move around

    1. 0.875 A
    2. 2.53 A
    3. 3.5 A
    4. 4.38 A
    Show the answer & worked solution

    Answer: D.4.38 A

    Primary pickup =420×1.25=525=420\times1.25=525 A, set above the maximum load so the relay never operates on load current; reflected through the 600:5 CTs, tap =525×5600=4.38=525\times\dfrac{5}{600}=4.38 A secondary. With wye-connected CTs the relay sees the line current one-for-one through the ratio, so no 3\sqrt3 enters. The other options set the tap right at full load, leaving out the margin (3.5 A); divide by 600 instead of 600/5, dropping the 5 A secondary (0.875 A); and divide by 3\sqrt3 as though converting a line current to a phase current (2.53 A).
  8. 8
    medium
    A. Machine types and applications
    The 4-pole, 60 Hz induction motor shown runs at a full-load slip of 4% while delivering 150 lb-ft of torque to its load. Its full-load shaft output is most nearly:
    Figure for this questionMBus4-pole150 lb-ft

    Figure — drag or pinch to move around

    1. 36.8 hp
    2. 49.4 hp
    3. 51.4 hp
    4. 98.7 hp
    Show the answer & worked solution

    Answer: B.49.4 hp

    Synchronous speed (§4.2.1.2): ns=120fp=120(60)4=1800n_s=\dfrac{120f}{p}=\dfrac{120(60)}{4}=1800 rpm. Shaft speed from the slip (§4.2.1.3): n=ns(1−s)=1800(1−0.04)=1728n=n_s(1-s)=1800(1-0.04)=1728 rpm. The handbook's power relation (§4.2.1.1) is in SI units, so convert the torque with the §1.2 table: T=150×1.356=203.4T=150\times1.356=203.4 N·m, then P=Tn9549=203.4(1728)9549=36.81P=\dfrac{Tn}{9549}=\dfrac{203.4(1728)}{9549}=36.81 kW, and 36.81×1.341=49.436.81\times1.341=49.4 hp. (The US-customary shortcut hp=T n/5252\text{hp}=T\,n/5252, with TT in lb-ft, gives the same result.) Distractors: 51.4 hp uses the 1800 rpm synchronous speed instead of the 1728 rpm shaft speed; 36.8 hp is the correct 36.8 kW reported as hp, without the kW-to-hp conversion; and 98.7 hp puts the 2 pole pairs in place of the 4 poles in 120f/p120f/p, doubling the speed.
  9. 9
    medium
    A. Voltage drop
    A three-phase, 480 V feeder runs 320 ft one way to a balanced load drawing 290 A at 0.95 lagging power factor. Each phase conductor has R=0.0258 ΩR=0.0258\ \Omega/1,000 ft and X=0.039 ΩX=0.039\ \Omega/1,000 ft. By the approximate method, the voltage drop as a percent of the nominal system voltage is most nearly:
    Figure for this question480 V busR + jX per kftLoad busI, PF lagI

    Figure — drag or pinch to move around

    1. 0.71%
    2. 0.86%
    3. 1.23%
    4. 1.42%
    Show the answer & worked solution

    Answer: C.1.23%

    Use the handbook's approximate line-to-neutral drop for a balanced three-phase load (§5.1.1), VDln≈I[R⋅PF+Xsin⁡(cos⁡−1PF)]VD_{ln}\approx I\left[R\cdot PF+X\sin(\cos^{-1}PF)\right], with RR and XX the per-phase ohms of the 320 ft run: R=0.0258(320/1,000)=0.008256 ΩR=0.0258(320/1{,}000)=0.008256\ \Omega and X=0.039(320/1,000)=0.01248 ΩX=0.039(320/1{,}000)=0.01248\ \Omega. With sin⁡(cos⁡−10.95)=0.312\sin(\cos^{-1}0.95)=0.312, VDln=290(0.007843+0.003897)=290(0.01174)=3.40VD_{ln}=290(0.007843+0.003897)=290(0.01174)=3.40 V. The line-to-line drop is 3×3.40=5.90\sqrt3\times3.40=5.90 V, so %VD=5.90/480×100=1.23%\%VD=5.90/480\times100=1.23\% of the nominal voltage. The other options come from the line-to-neutral drop divided by the line-to-line voltage; the unity-PF form 2LRI/(K⋅1,000)2LRI/(K\cdot1{,}000) with K=2/3K=2/\sqrt3, which ignores the power factor and the reactance; and the single-phase factor 2 in place of 3\sqrt3.
  10. 10
    medium
    B. Symmetrical components
    During a ground fault, the phase-to-neutral voltages measured at a bus are Va=35∠0∘V_a = 35\angle{0}^\circ V, Vb=105∠−128∘V_b = 105\angle{-128}^\circ V, and Vc=125∠120∘V_c = 125\angle{120}^\circ V, as shown in the phasor diagram. The zero-sequence voltage Va0V_{a0} is most nearly:
    Figure for this questionReImVaVbVc

    Figure — drag or pinch to move around

    1. 22.6∠−170.7∘22.6\angle{-170.7}^\circ V
    2. 31.9∠164.5∘31.9\angle{164.5}^\circ V
    3. 88.1∠−3.2∘88.1\angle{-3.2}^\circ V
    4. 95.6∠164.5∘95.6\angle{164.5}^\circ V
    Show the answer & worked solution

    Answer: B.31.9∠164.5∘31.9\angle{164.5}^\circ V

    The zero-sequence voltage is the first row of the handbook's symmetrical-component transformation (§3.1.2): Va0=13(Va+Vb+Vc)V_{a0}=\tfrac13(V_a+V_b+V_c), a plain phasor sum with no aa-operator rotations. In rectangular form Va=35+j0V_a=35+j0, Vb=−64.6−j82.7V_b=-64.6-j82.7 and Vc=−62.5+j108.3V_c=-62.5+j108.3 V, so Va+Vb+Vc=−92.1+j25.5V_a+V_b+V_c=-92.1+j25.5 V == 95.6∠164.5∘95.6\angle{164.5}^\circ V, and Va0=V_{a0}= 31.9∠164.5∘31.9\angle{164.5}^\circ V. Distractors: 95.6∠164.5∘95.6\angle{164.5}^\circ V is the phasor sum itself, 3Va03V_{a0} (the residual voltage), with the factor 13\tfrac13 left off; 22.6∠−170.7∘22.6\angle{-170.7}^\circ V is Va2V_{a2}: it uses the third (negative-sequence) row, 13(Va+a2Vb+aVc)\tfrac13(V_a+a^2V_b+aV_c); and 88.1∠−3.2∘88.1\angle{-3.2}^\circ V is Va1V_{a1}: it uses the second (positive-sequence) row, 13(Va+aVb+a2Vc)\tfrac13(V_a+aV_b+a^2V_c).

That was ten. There are 4,700+ more.

The full PE Electrical and Computer: Power bank covers every knowledge area, with full-length timed mock exams at the real exam's 80 questions and time limit, and an AI tutor to talk any problem through.

Studying for a different exam? See free practice problems for all 11 exams, or read our FE & PE study guides.

These ten are among the free sample questions anyone can practice in the app, no account needed. The paid bank is separate. Independent study resource; not affiliated with, endorsed by, or sponsored by NCEES.