Skip to main content
FE to PEPrep

Free PE Power practice problems

Ten real questions from our PE Electrical and Computer: Power bank — one from each knowledge area, with the same exam-realistic figures and fully worked solutions our members get. No signup, no email. Try each one first, then reveal the solution.

10 with figures9 knowledge areasFull worked solutions
  1. 1
    medium
    A. Three-phase circuits
    A three-phase induction motor delivers 50 hp at full load. At this load its efficiency is 91% and its power factor is 0.86 lagging. The motor is supplied at 480 V (line-to-line). The full-load line current is most nearly:
    Figure for this questionMILVLN
    1. 57.3 A
    2. 99.3 A
    3. 52.2 A
    4. 49.3 A
    Show the answer & worked solution

    Answer: A.57.3 A

    Pout=50×746=37.3P_{out}=50\times746=37.3 kW; Pin=Pout/η=37.3/0.91=40.99P_{in}=P_{out}/\eta=37.3/0.91=40.99 kW; S=Pin/pf=47.66S=P_{in}/pf=47.66 kVA; I=S/(3VLL)=47.66×103/(3×480)=57.3I=S/(\sqrt3\,V_{LL})=47.66\times10^3/(\sqrt3\times480)=57.3 A. Distractors forget the efficiency (use shaft output as electrical input), forget the power factor (treat PinP_{in} as kVA), and drop the 3\sqrt3.
  2. 2
    medium
    E. Testing
    A transformer turns-ratio (TTR) test set is connected to a single-phase transformer rated 13800–480 V on the nominal tap, so the nameplate voltage ratio equals the turns ratio. The set measures a ratio of 28.95. The ratio error relative to nameplate is most nearly — and does the transformer pass the ±0.5% acceptance criterion?
    Figure for this questionTTR test set13800:480 Vunder testX1–X2
    1. -0.7% — fail (outside ±0.5%)
    2. +0.7% — fail (outside ±0.5%)
    3. +0.2% — pass
    4. +0.7% — pass
    Show the answer & worked solution

    Answer: B.+0.7% — fail (outside ±0.5%)

    Nameplate ratio =13800/480=28.75=13800/480=28.75. Error =28.9528.7528.75×100=+0.7%=\dfrac{28.95-28.75}{28.75}\times100=+0.7\%, which is outside the ±0.5% band, so the unit fails. Distractors keep the right number but flip the pass-band verdict, reverse the sign (calling a high ratio low), and report the raw ratio difference +0.2 as if it were already a percent.
  3. 3
    medium
    C. Special occupancies and systems
    A hospital's Type 1 essential electrical system is divided per the governing code (rules given): the life safety branch carries only the functions essential for life safety (egress lighting, exit signs, alarm and emergency communication systems); the critical branch carries task illumination, fixed equipment, and selected receptacles serving patient care — both branches must be restored automatically within 10 seconds. The equipment branch carries major mechanical loads (medical air/vacuum, HVAC, pumps) on delayed-automatic or manual connection. To which portion of the system should the corridor egress illumination and exit signs along the means of egress be connected?
    Figure for this questionGNormal sourceserviceGeneratoralternateATS10 sEssential busLife safetyCriticalEquipment
    1. Nonessential (normal system) loads
    2. Critical branch
    3. Equipment branch
    4. Life safety branch
    Show the answer & worked solution

    Answer: D.Life safety branch

    The described load falls squarely in the life safety branch scope: functions essential for life safety — egress illumination, exit signs, alarm and emergency communication — restored automatically within 10 seconds. The distractors assign it to the wrong portion of the system: the critical branch serves task illumination, fixed equipment, and selected receptacles serving patient care, restored automatically within 10 seconds; the equipment branch serves major mechanical/three-phase loads (medical air and vacuum, HVAC, pumps) on delayed-automatic or manual connection; the nonessential (normal system) loads serves ordinary building loads that are permitted to remain de-energized on loss of normal power — none of which matches this load's function.
  4. 4
    medium
    B. Surge protection
    A metal-oxide surge arrester is being selected for a 12.47 kV (line-to-line), effectively grounded distribution system that may operate continuously at 105% of nominal voltage. Standard arrester MCOV values are 2.55, 5.1, 7.65, 8.4, 10.2, 12.7, 15.3, 19.5, 22, and 24.4 kV. The minimum standard MCOV suitable for this application is:
    Figure for this questionUtility12.47 kVeffectively groundedMOV arresterMCOV = ?transformerload
    1. 8.4 kV
    2. 7.65 kV
    3. 15.3 kV
    4. 5.1 kV
    Show the answer & worked solution

    Answer: B.7.65 kV

    Required MCOV1.05×12.47/3=7.56MCOV \ge 1.05\times12.47/\sqrt3 = 7.56 kV; the smallest standard value at or above this is 7.65 kV. Distractors round DOWN to 5.1 kV (the arrester would conduct continuously and thermally run away), over-select 8.4 kV (raising the discharge voltage and eroding the protective margin for no reason), and size from the full line-to-line voltage instead of line-to-ground, forcing 15.3 kV.
  5. 5
    medium
    B. Insulation testing
    An insulation-resistance test on a motor winding is recorded at three points: 160 megohm at 30 seconds, 200 megohm at 1 minute and 500 megohm at 10 minutes. Compute the Polarization Index (PI) and classify the insulation.
    Figure for this questionRt1 min10 min
    1. PI = 1.25 — questionable
    2. PI = 2.5 — questionable
    3. PI = 2.5 — good
    4. PI = 0.4 — investigate
    Show the answer & worked solution

    Answer: C.PI = 2.5 — good

    PI=R10/R1=500/200=2.5PI=R_{10}/R_{1}=500/200=2.5, which is good per IEEE 43. Distractors invert the ratio; compute the dielectric absorption ratio DAR=R1min/R30s=200/160=1.25DAR=R_{1\,min}/R_{30\,s}=200/160=1.25 instead — DAR is a different index taken off the early capacitive part of the curve, not the 1-to-10-minute polarization tail the PI measures; and misread the acceptance band.
  6. 6
    medium
    B. Relays, switches, Boolean and ladder logic
    The figure shows a three-wire motor-control circuit: an NC Stop pushbutton and an NO Start pushbutton in series with the NC overload (OL) contact and the M contactor coil, with an M auxiliary contact connected in parallel with the Start pushbutton (seal-in). The motor is initially off and the Start pushbutton is pressed and released. What does the M contactor do?
    Figure for this questionL1L2Stop PBStart PBOLMM aux (seal-in)
    1. M does not pick up until the Stop pushbutton is also pressed
    2. M cannot pick up at all, because the M auxiliary contact is open until the coil energizes
    3. M picks up when Start is pressed and remains energized after release — the M auxiliary contact seals in around the Start pushbutton
    4. M is energized only while Start is held and drops out as soon as it is released
    Show the answer & worked solution

    Answer: C.M picks up when Start is pressed and remains energized after release — the M auxiliary contact seals in around the Start pushbutton

    At rest the NC Stop and NC OL contacts are closed. Pressing Start completes the rung, M energizes, and the M auxiliary (NO) contact closes in parallel with Start; on release, coil current flows through that seal-in path, so M stays picked up. The first distractor ignores the seal-in branch (two-wire control behavior); the second wrongly places the M auxiliary contact in series with Start instead of in parallel; the third misreads the NC Stop as a contact that must be actuated to close.
  7. 7
    medium
    B. Protective relaying (differential, distance, undervoltage, pilot)
    A line distance (21) relay protects a line whose positive-sequence impedance is 24 Ω24\ \Omega primary. The relay is supplied by 1200:5 CTs and 14400:120 V VTs. With Zone 1 set to 80% of the line, the Zone 1 reach in secondary (relay) ohms is most nearly:
    Figure for this questionBus S (21)ZL = 24 ohmBus RZone 1 = 80%
    1. 38.4 ohm secondary
    2. 9.6 ohm secondary
    3. 19.2 ohm secondary
    4. 48 ohm secondary
    Show the answer & worked solution

    Answer: A.38.4 ohm secondary

    CTR =240=240, VTR =14400/120=120=14400/120=120, so Zsec=Zpri×CTRVTR=24×2=48 ΩZ_{sec}=Z_{pri}\times\dfrac{CTR}{VTR}=24\times2=48\ \Omega. Zone 1 =0.8×48=38.4 Ω=0.8\times48=38.4\ \Omega secondary — deliberately short of the remote bus so measurement errors cannot cause an instantaneous overreach trip for the next line's faults. Distractors invert the CTR/VTR factor, forget the 80% margin (setting Zone 1 to the full line), and leave the reach in primary ohms.
  8. 8
    medium
    C. Power factor correction
    A plant load draws 600 kW at 0.72 lagging power factor. A 300 kvar capacitor bank (standard-size units) is switched onto the plant bus. The resulting power factor is most nearly:
    Figure for this questionUtilityPlant busQC bankP, PF1 lag
    1. 0.949
    2. 0.907
    3. 0.894
    4. 0.564
    Show the answer & worked solution

    Answer: B.0.907

    Q1=Ptan(cos10.72)=600×0.9639=578.3Q_1=P\tan(\cos^{-1}0.72)=600\times0.9639=578.3 kvar. Remaining Q=578.3300=278.3Q=578.3-300=278.3 kvar, so PFnew=cos(tan1278.3600)=0.907PF_{new}=\cos\left(\tan^{-1}\dfrac{278.3}{600}\right)=0.907. Distractors add the capacitor kvar instead of subtracting (sign error), treat the bank rating itself as the remaining reactive power, and divide the remaining kvar by the kVA instead of the kW.
  9. 9
    medium
    A. Machine types and applications
    The 4-pole, 60 Hz induction motor shown delivers 150 lb-ft of torque at its full-load speed of 1746 rpm. Its shaft output is most nearly:
    Figure for this questionVFDM460 V bus4-pole150 lb-ft
    1. 451 hp
    2. 51.4 hp
    3. 49.9 hp
    4. 7.94 hp
    Show the answer & worked solution

    Answer: C.49.9 hp

    hp=TN5252=150×17465252=49.9hp=\dfrac{TN}{5252}=\dfrac{150\times1746}{5252}=49.9 hp. Distractors divide by 33000 without the 2π2\pi (the 5252 already folds in 2π/330002\pi/33000), invert the relation as 5252T/N5252T/N, and use the 1800 rpm synchronous speed instead of the actual shaft speed.
  10. 10
    medium
    B. Symmetrical components
    The phase voltages on an unbalanced feeder are measured as Va=1200V_a = 120\angle 0^\circ V, Vb=90120V_b = 90\angle -120^\circ V, and Vc=60120V_c = 60\angle 120^\circ V. The zero-sequence component V0V_0 is most nearly:
    Figure for this questionReImVaVbVc
    1. 90090\angle 0^\circ V
    2. 17.33017.3\angle -30^\circ V
    3. 523052\angle -30^\circ V
    4. 17.33017.3\angle 30^\circ V
    Show the answer & worked solution

    Answer: B.17.33017.3\angle -30^\circ V

    V0=13(Va+Vb+Vc)V_0=\tfrac13(V_a+V_b+V_c). The phasor sum is 523052\angle -30^\circ V, so V0=V_0= 17.33017.3\angle -30^\circ V. Distractors: 523052\angle -30^\circ V forgets the factor 1/3; 90090\angle 0^\circ V averages the magnitudes and ignores the angles; 17.33017.3\angle 30^\circ V applies aa-operator rotations (a negative-sequence calculation) that do not belong in V0V_0.

That was ten. There are thousands.

The full PE Electrical and Computer: Power bank covers every knowledge area at this depth, with timed mock exams that mirror the real 80-question paper and an AI tutor grounded in the NCEES PE Power Reference Handbook + NEC 2020 & NESC 2017 — so it can't confidently feed you a wrong answer.

Studying for a different exam? See free practice problems for all 11 exams, or read our FE & PE study guides.

These are the same free sample questions available to anyone with an account — the paid bank is separate. Independent study resource; not affiliated with, endorsed by, or sponsored by NCEES.