HVAC Controls & Instrumentation · Study · PE Mechanical: HVAC and Refrigeration · FE → PE Prep
HVAC Controls & Instrumentation
5% of exam
Valve and damper authority and Cv, sensors and actuators, economizer and reset strategies, and PID feedback response.
4 concepts
D. Control Concepts
Control-Valve Sizing: Cv, Authority and Characteristic
Size a modulating valve from its flow coefficient, protect controllability with valve authority, and match an equal-percentage trim to a nonlinear coil for linear control.
A modulating valve is the muscle of every hydronic loop: the controller decides how much heating or cooling a coil should deliver, and the valve translates that decision into a flow rate. Get the valve too big and the first few percent of stroke dumps nearly full flow — the loop becomes an on/off switch that hunts and overshoots. Get the characteristic wrong and a coil that is already nonlinear fights the controller across the whole range. The PE Mechanical exam tests three linked ideas that decide whether a valve actually controls: the flow coefficient Cv
that sizes it, the authority
β
that preserves its shape once installed, and the inherent characteristic chosen to linearize the coil. All three live in the handbook's §11.3 Control Valves (PE Mechanical Reference Handbook — §11 Temperature Controls).
The flow coefficient Cv
The valve flow coefficient is defined as the flow of 60∘F water, in gpm, that a fully open valve passes at a 1psi pressure drop. It bundles the valve's geometry into one number you can size against. For any other water flow and drop the relation is a square-root law — flow varies with the square root of the pressure drop — and for fluids other than water you correct with specific gravity Sg. Sizing a control valve means picking a Cv such that the valve takes a deliberate, healthy pressure drop at design flow; a valve sized to take almost no drop has nothing to control with.
The inherent characteristic is the flow-versus-stroke curve measured at constant pressure drop. A linear valve gives flow directly proportional to stem position. A quick-opening valve dumps most of its flow in the first part of the stroke — fine for two-position service, useless for modulation. An equal-percentage valve raises flow by the same percentage of the current flow for each equal increment of stroke, so it is gentle near closed and aggressive near open. That exponential shape is set by the rangeability R (the ratio of maximum to minimum controllable flow), and it is the workhorse trim for modulating hydronic coils.
Valve authority: why the installed curve is not the catalog curve
The catalog characteristic assumes constant pressure drop across the valve. In a real circuit, the coil, balancing valve, fittings, and pipe share the pump head with the valve, and as the valve closes its share of the drop rises while the rest of the circuit's drop falls. Authority β is the ratio of the valve's pressure drop at full flow to the total variable pressure drop of the controlled branch at full flow — the open valve plus everything in series with it. Low authority means the valve takes only a sliver of the branch drop when open, so closing it barely changes flow at first and then collapses flow suddenly: the installed curve bends toward quick-opening and controllability is lost. Designers target β≥0.5 (and rarely below 0.25) precisely to keep the installed curve close to the inherent one.
You can quantify the distortion. If f=q/qmax is the inherent flow fraction at a given stroke and β is the authority, the installed flow fraction φ follows the relation below. At full stroke f=1 and φ=1 regardless of authority; everywhere else, lower authority pushes φ above f, fattening the low-stroke end of the curve. This is the math behind the rule of thumb: an equal-percentage valve at β≈0.5 comes out roughly linear once installed, which is exactly what a typical coil wants.
φ=β+(1−β)f2f
Matching the valve to the coil
A hot-water or chilled-water coil is itself strongly nonlinear: the first 20–30% of flow delivers more than half the capacity because heat transfer is limited by the air side, so capacity rises steeply at low flow and flattens at high flow. Put a linear valve on such a coil and a small early stroke produces a huge capacity jump — poor control. Put an equal-percentage valve on it and the valve's gentle low-stroke behavior cancels the coil's steep low-flow behavior, yielding capacity nearly proportional to control signal. That cancellation only survives if authority is high enough to keep the installed characteristic equal-percentage rather than quick-opening — which is why sizing Cv for a real pressure drop and checking β are the same design act.
control signalequal % valveflownonlinear coilcapacity≈linear
Two-way vs three-way and rangeability
Two-way valves throttle flow and create variable-flow systems; pairing them with a variable-speed pump and a differential-pressure setpoint is standard modern practice. Three-way valves (mixing or diverting) keep branch flow roughly constant by bypassing — constant-flow systems, older or specialty applications. Rangeability sets how far down you can turn before control collapses: a valve with R=50 controls down to 2% of rated flow, but only over the portion of stroke where authority keeps the curve honest. Oversizing throws away rangeability, because design flow then occurs at a small stroke where the valve resolution is coarse and authority is already poor.
Exam strategy
Lead with the square-root law: Cv=QSg/ΔP, and remember it is defined for water at a 1psi drop, so for water Sg=1 and Cv=Q/ΔP. When asked to size, solve for the Cv that gives a design valve drop in the 3–10psi band, then back-check the actual drop at the catalog Cv you would pick. For authority questions, write β as valve-open drop over total branch-open drop and compare to 0.5; if it is low, the cure is a smaller Cv (more valve drop), not a different characteristic. If a problem mentions linear heat transfer or a nonlinear coil, the intended answer is almost always equal-percentage trim. Keep ΔP in psi and Q in gpm to stay consistent with the handbook definition.
Key equations
Flow coefficient (general fluid)Cv=QΔPSg
Q in gpm, ΔP across the valve in psi, Sg = specific gravity (1.0 for water). Defines the valve size.
Flow from CvQ=CvSgΔP
Cv for waterCv=ΔPQ
Equal-percentage characteristicqmaxq=R(x−1)
RangeabilityR=qminqmax
Valve authorityβ=ΔPbranch, openΔPvalve, open
Installed characteristicφ=β+(1−β)f2f
Valve gaingain=ΔxΔq
Slope of the installed flow-vs-stroke curve. Good control wants this roughly constant across the operating range.
Worked examples
Sizing a chilled-water coil valve
Problem. A two-way modulating valve must pass 60gpm of chilled water to a coil. The designer allots a 6psi drop across the wide-open valve. (a) Find the required Cv. (b) If the nearest catalog valve is Cv=25, what drop will the valve actually take at 60gpm?
Solution. Water, so Sg=1.
(a) Cv=Q/ΔP=60/6=60/2.449=24.5
Cv=660=24.5,ΔP25=(2560)2=5.76psi
Checking valve authority
Problem. A heating coil branch at design flow has the following pressure drops: coil 4.5psi, balancing valve 1.5psi, fittings and pipe 1.0psi. The wide-open control valve is sized for 7.0psi. (a) Compute the valve authority. (b) Is controllability acceptable? (c) If instead the valve were sized for only 2.0psi
Installed flow at mid-stroke
Problem. An equal-percentage valve with rangeability R=50 is installed at authority β=0.50. (a) What inherent flow fraction occurs at 50% stroke? (b) What installed flow fraction does that produce? (c) Compare to a poorly sized installation at β=0.25.
•Oversizing the valve so it takes almost no design drop: the first few percent of stroke then passes most of the flow, the loop short-cycles, and rangeability is wasted. Size for a deliberate 3–10psi valve drop.
•Confusing inherent and installed characteristics. The catalog curve is at constant ΔP; in a circuit the curve distorts by authority. Always check β before trusting the published shape.
•Computing authority against the whole pump head instead of the controlled branch's variable drop. Use the open-valve drop over the series valve + coil + balancing + fitting drop of that branch.
•Putting a linear valve on a nonlinear coil and expecting linear capacity. The coil's steep low-flow capacity needs an equal-percentage valve to cancel it.
•Forgetting the ΔP law. Flow does not scale linearly with pressure drop; halving flow needs a quarter of the drop at fixed opening.
•Dropping the specific-gravity correction for glycol or other fluids. Use Cv=QSg/ΔP
•Using a butterfly or standard ball valve for modulation. Per the handbook, those are two-position devices; only a characterized ball or a globe valve modulates well.
References
NCEES PE Mechanical Reference Handbook — §11 Temperature Controls (§11.3 Control Valves)
ASHRAE Handbook — Fundamentals, Ch. 7 Fundamentals of Control
ASHRAE Handbook — HVAC Systems and Equipment, Valve characteristics and selection
PID Feedback, Reset Schedules and Economizers
How proportional, integral, and derivative action shape a feedback loop, why proportional-only control leaves offset, and how reset schedules and economizer changeover save energy.
Unlocks with an access pass — one-time payment, no auto-renew. View passes
Pass holders
Control Dampers: Authority, Types and Normal Position
Parallel- vs opposed-blade damper characteristics, damper authority, sizing for controllable mixing by face velocity, and choosing fail-safe normal positions.
Unlocks with an access pass — one-time payment, no auto-renew. View passes
Pass holders
Sensors, Transmitters and Actuators
Temperature, pressure, humidity, and flow sensing; transmitter range and span; the 4–20 mA and 0–10 V signals; and pneumatic, electric, and electronic actuators.
Unlocks with an access pass — one-time payment, no auto-renew. View passes
Pass holders
Square-root law: flow through a fixed opening scales with ΔP. Use to back-check actual drop at a chosen Cv.
Sg=1 simplification. Cv equals the gpm of 60∘F water at 1psi drop.
x = fractional stroke (0–1), R = rangeability (max/min controllable flow). Flow rises by a constant percentage per equal stroke step.
Ratio of maximum to minimum controllable flow at a stated characteristic; larger is better for turndown.
Open-valve drop divided by total variable branch drop (valve + coil + balancing + fittings) at full flow. Target β≥0.5.
Maps inherent flow fraction f to installed flow fraction φ given authority β. Lower β distorts toward quick-opening.
.
(b) Rearranging the square-root law,
ΔP=(Q/Cv)2=(60/25)2=(2.40)2=5.76psi
.
The
Cv=25
valve takes
5.76psi
at design flow — close to the
6psi
allotment, so it is a good selection. Sanity check: a larger
Cv
would take less drop and weaken authority, so rounding up only slightly is correct.
, what authority results?
Solution. Series 'rest of branch' drop: ΔPrest=4.5+1.5+1.0=7.0psi.
(a) β=ΔPvalve+ΔPrestΔPvalve=7.0+7.07.0=0.500.
(b) β=0.50 meets the usual β≥0.5 target, so the installed characteristic stays close to the inherent equal-percentage shape — acceptable control.
(c) With a 2.0psi valve: β=2.0/(2.0+7.0)=0.222. That is below 0.25, so the installed curve would distort toward quick-opening and control would degrade.
Sanity check: bigger valve drop (smaller Cv) raises authority — consistent with the trade-off that good control costs pump head.
β=7.0+7.07.0=0.500
, i.e.
14.1%
flow at half stroke — the gentle low-end of equal percentage.
(b) Installed at