HVAC Controls & Instrumentation
Valve and damper authority and Cv, sensors and actuators, economizer and reset strategies, and PID feedback response.
4 concepts
Valve and damper authority and Cv, sensors and actuators, economizer and reset strategies, and PID feedback response.
4 concepts
Size a modulating valve from its flow coefficient, protect controllability with valve authority, and match an equal-percentage trim to a nonlinear coil for linear control.
Q in gpm, ΔP across the valve in psi, Sg = specific gravity (1.0 for water). Defines the valve size.
Square-root law: flow through a fixed opening scales with ΔP. Use to back-check actual drop at a chosen Cv.
Sg=1 simplification. Cv equals the gpm of 60∘F water at 1psi drop.
x = fractional stroke (0–1), R = rangeability (max/min controllable flow). Flow rises by a constant percentage per equal stroke step.
Ratio of maximum to minimum controllable flow at a stated characteristic; larger is better for turndown.
Open-valve drop divided by total variable branch drop (valve + coil + balancing + fittings) at full flow. Target β≥0.5.
Maps inherent flow fraction f to installed flow fraction φ given authority β. Lower β distorts toward quick-opening.
Slope of the installed flow-vs-stroke curve. Good control wants this roughly constant across the operating range.
Sizing a chilled-water coil valve
Problem. A two-way modulating valve must pass 60gpm of chilled water to a coil. The designer allots a 6psi drop across the wide-open valve. (a) Find the required Cv. (b) If the nearest catalog valve is Cv=25, what drop will the valve actually take at 60gpm?
Checking valve authority
Problem. A heating coil branch at design flow has the following pressure drops: coil 4.5psi, balancing valve 1.5psi, fittings and pipe 1.0psi. The wide-open control valve is sized for 7.0psi. (a) Compute the valve authority. (b) Is controllability acceptable? (c) If instead the valve were sized for only 2.0psi, what authority results?
Installed flow at mid-stroke
Problem. An equal-percentage valve with rangeability R=50 is installed at authority β=0.50. (a) What inherent flow fraction occurs at 50% stroke? (b) What installed flow fraction does that produce? (c) Compare to a poorly sized installation at β=0.25.
How proportional, integral, and derivative action shape a feedback loop, why proportional-only control leaves offset, and how reset schedules and economizer changeover save energy.
Unlocks with an access pass — one-time payment, no auto-renew. View passes
Parallel- vs opposed-blade damper characteristics, damper authority, sizing for controllable mixing by face velocity, and choosing fail-safe normal positions.
Unlocks with an access pass — one-time payment, no auto-renew. View passes
Temperature, pressure, humidity, and flow sensing; transmitter range and span; the 4–20 mA and 0–10 V signals; and pneumatic, electric, and electronic actuators.
Unlocks with an access pass — one-time payment, no auto-renew. View passes