Psychrometrics & Air Processes · Study · PE Mechanical: HVAC and Refrigeration · FE → PE Prep
Psychrometrics & Air Processes
14% of exam
Moist-air properties, the psychrometric chart, and sensible, latent, mixing, humidification, and dehumidification processes at sea level and altitude.
6 concepts
B. Heating/Cooling Processes
Moist-Air Properties and the Psychrometric Chart
The six interlocking properties of moist air — dry-bulb, wet-bulb, dew point, humidity ratio, enthalpy, specific volume — and how to fix a state and read processes on the chart.
Almost every HVAC and refrigeration problem on this exam begins by fixing the state of moist air, and almost every wrong answer traces back to a state read incorrectly. Moist air is a two-component mixture — dry air plus a little water vapor — so it takes exactly two independent intensive properties to pin the state at a fixed total pressure. Give the exam any two of dry-bulb temperature, wet-bulb temperature, dew point, humidity ratio, relative humidity, or enthalpy, and the psychrometric chart hands you all the rest in seconds. The NCEES PE Mechanical Reference Handbook collects the governing relations in §7 Psychrometrics, but the chart is what you will actually use under time pressure, so this concept builds fluency in both the equations behind the chart and the act of reading it.
Humidity ratio is the conserved bookkeeping variable
Humidity ratio W
is the mass of water vapor carried by each pound of dry air,
W=Mw/Mda
, in
lbw/lbda
(or grains, with
7000gr=1lbw
). It is the natural conserved quantity for air processes because the dry-air mass flow never changes as air is heated, cooled, humidified, or mixed — only the water riding along with it does. In terms of partial pressures it follows directly from the ideal-gas mole ratio scaled by the molar-mass ratio
18.015/28.966≈0.62194
(rounded to the conventional ASHRAE constant
0.62198
):
W=0.62198p−pwpw
Relative humidity, dew point, and saturation
Relative humidity ϕ is the ratio of the actual vapor mole fraction to its saturated value at the same temperature and pressure, very nearly ϕ=pw/pws(t), where pws(t) is the saturation pressure of water at the dry-bulb temperature. Dew point td is the temperature to which you must cool the air at constant pressure and constant W until it first saturates — that is, until pws(td)=pw. Saturation humidity Ws(t,p) is the largest W the air can hold at that temperature; degree of saturation is μ=W/Ws. Dew point is set by W alone and is therefore the cleanest indicator of absolute moisture content.
ϕ=pws(t)pw,td:pws(td)=pw
Wet-bulb temperature: the chart's diagonal
The thermodynamic wet-bulb temperature t∗ is the temperature reached when water evaporates adiabatically into the airstream until it saturates at constant total pressure. It is depressed below the dry-bulb whenever the air is unsaturated, and the dry-bulb, wet-bulb, and dew point all collapse to one value at saturation. The ASHRAE working relation (ASHRAE Handbook—Fundamentals, Ch. 1) for W from a measured dry-bulb t and wet-bulb t∗ (with Ws∗ the saturation humidity at t∗) is the equation you use whenever a sling-psychrometer reading is given; the NCEES handbook itself gives W only from the partial pressures, so reach for this correlation when only the two temperatures are reported:
W=1093+0.444t−t∗(1093−0.556t∗)Ws∗−0.240(t−t∗)
Enthalpy and specific volume
Specific enthalpy is referenced to a pound of dry air, not a pound of mixture: h=0.240t+W(1061+0.444t) in Btu/lbda, where the first term is dry-air sensible heat and the parenthesis is the vapor's latent-plus-sensible content. Lines of constant enthalpy on the chart run almost parallel to constant wet-bulb lines — close, but not identical, which matters in precise work. Specific volume is also per pound of dry air, v=0.370(t+459.67)(1+1.6078W)/p in ft3/lbda; you need it to convert between volumetric airflow (CFM) and the mass flow that actually carries the energy.
h=0.240t+W(1061+0.444t)
Locating a state and reading a process
Plot a state by walking in from any two property scales: dry-bulb along the bottom, humidity ratio up the right edge, wet-bulb and enthalpy along the upper-left diagonal scale, relative-humidity as the family of curves, with saturation as the leftmost boundary. Once the point is fixed, a process is just an arrow. A horizontal arrow (constant W) is pure sensible heating or cooling; a vertical arrow (constant dry-bulb) is pure latent change; an arrow up-and-left at constant wet-bulb is adiabatic humidification. Reading the endpoints off the chart and differencing the properties is the entire method.
Exam strategy
Identify the two independent properties the problem gives, fix the state, and only then compute. When given a sling psychrometer's dry-bulb and wet-bulb, use the ASHRAE wet-bulb relation or the chart; do not confuse wet-bulb with dew point unless the air is saturated. Carry humidity ratio in lbw/lbda for energy balances and convert to grains only for the 0.68 coefficient. Remember that h and v are per pound of dry air, so a CFM-to-mass conversion always divides volumetric flow by the specific volume at the state in question, never by a generic 13.33ft3/lb unless the state truly is standard air.
Key equations
Humidity ratio from partial pressuresW=0.62198p−pwpw
W in lbw/lbda; pw
Saturation humidity ratioWs=0.62198p−pwspws
Relative humidityϕ=pws(t)pw
Dew point conditionpws(td)=pw
td
Humidity ratio from wet-bulbW=1093+0.444t−t∗(1093−0.556t∗)Ws∗−0.240(t−t∗)
Moist-air specific enthalpyh=0.240t+W(1061+0.444t)
Btu/lbda
Moist-air specific volumev=p0.370(t+459.67)(1+1.6078W)
ft3/lbda
Degree of saturationμ=Ws(t,p)W
Dimensionless; close to but not equal to relative humidity ϕ
Worked examples
Fix a state from dry-bulb and wet-bulb
Problem. Air at sea level (p=14.696psia) reads 80∘F dry-bulb and 67∘F wet-bulb. Find the humidity ratio, relative humidity, enthalpy, specific volume, and dew point.
Solution. Saturation humidity at the wet-bulb: pws(67)=0.3277psia, so Ws∗=0.62198(0.3277)/(14.696−0.3277)=0.01419
W=1061.5(1055.7)(0.01419)−3.12=0.0112lbw/lbda
Convert CFM to dry-air mass flow
Problem. An air handler delivers 4000CFM of the 80∘F/67∘F air above (v=13.8ft3/lbda
Common pitfalls
•Confusing wet-bulb with dew point. They coincide only at saturation; for the 80/67 air above, t∗=67∘F but td=60∘F. Dew point tracks W; wet-bulb tracks enthalpy.
•Treating h and v as per pound of MIXTURE. Both are referenced to a pound of DRY air, so CFM-to-mass conversions divide by the moist-air specific volume v in ft3/lbda
•Using ϕ=W/Ws as exact. That ratio is the degree of saturation μ; relative humidity is the partial-pressure (mole-fraction) ratio and differs by a few percent.
•Reading the chart at the wrong pressure. A sea-level chart is only valid near sea level; at altitude the saturation curve and every property line shift (separate concept).
•Carrying humidity ratio in grains into an enthalpy or mass balance. Energy balances need lbw/lbda; grains are for the 0.68 latent coefficient only.
•Assuming standard air (v≈13.33ft3/lb, ρ=0.075lb/ft3) for every state. Use the actual specific volume at the actual temperature and humidity when precision matters.
References
NCEES PE Mechanical Reference Handbook — §7 Psychrometrics
NCEES PE Mechanical Reference Handbook — §7.4 Thermodynamic Properties of Moist Air
Sensible, Latent, Mixing and the 1.08 / 0.68 / 4.5 Coefficients
The standard-air airflow equations for sensible, latent, and total load, the sensible heat ratio, and how to mix two airstreams on the chart.
Unlocks with an access pass — one-time payment, no auto-renew. View passes
Pass holders
Altitude and Low-Temperature Corrections
Correcting air density and the 1.08 / 0.68 / 4.5 airflow coefficients for elevation, the pressure shift of the psychrometric chart, and low-temperature adjustments.
Unlocks with an access pass — one-time payment, no auto-renew. View passes
Pass holders
C. Humidification/Dehumidification
Cooling-Coil Process: ADP, Bypass Factor and the Coil Line
Apparatus dew point, bypass factor, the coil condition line, and grand-sensible-heat-ratio sizing of a cooling and dehumidifying coil.
Unlocks with an access pass — one-time payment, no auto-renew. View passes
Pass holders
Humidification and Evaporative Cooling (Adiabatic Saturation)
Adiabatic evaporative cooling along the wet-bulb line, steam versus adiabatic humidification, saturation effectiveness, and direct versus indirect evaporative cooling.
Unlocks with an access pass — one-time payment, no auto-renew. View passes
Pass holders
Desiccant Dehumidification and Low-Dew-Point Processes
Solid and liquid desiccant dehumidification, the sorption path on the chart, regeneration, and when desiccants beat cooling-coil dehumidification.
Unlocks with an access pass — one-time payment, no auto-renew. View passes
Pass holders
= vapor partial pressure,
p
= total pressure (psia).
7000gr=1lbw
.
Maximum W at temperature t; pws = saturation pressure of water at t (psia).
Ratio of actual to saturated vapor partial pressure at the same dry-bulb t and p.
= temperature where saturation pressure equals the actual vapor pressure; set by
W
alone.
t = dry-bulb, t∗ = wet-bulb (°F), Ws∗ = saturation humidity at t∗. ASHRAE USCS correlation (not in the NCEES handbook, which gives W only from partial pressures).
;
t
in °F. First term dry-air sensible, parenthesis vapor latent + sensible.
, exactly the required ordering for unsaturated air. Answers:
W=0.0112lbw/lbda
,
ϕ=51.1%
,
h=31.4Btu/lbda
,
v=13.8ft3/lbda
,
td=60.3∘F
.
). What dry-air mass flow does it move, and how much water vapor (lb/hr) rides along with it?
Solution. Dry-air mass flow: m˙da=vV˙=13.8ft3/lbda4000ft3/min=289.9lbda/min, i.e. m˙da×60=17,390lbda/hr.
Water carried: m˙w=Wm˙da=0.01117(17,390)=194lbw/hr.
Sanity check on the magnitude: standard air is 0.075lb/ft3, giving roughly 4000×0.075×60=18,000lb/hr of mixture — our dry-air value of 17,400lb/hr is just below that because this air is warmer and lighter than 70∘F standard air. Answers: m˙da=1.74×104lb/hr, m˙w=194lb/hr.