Heating & Cooling Loads
Envelope conduction, solar and internal gains, infiltration and ventilation loads, supply-air flow from room sensible heat, and reheat.
5 concepts
Envelope conduction, solar and internal gains, infiltration and ventilation loads, supply-air flow from room sensible heat, and reheat.
5 concepts
Build the overall U-factor from series and parallel thermal resistances, then drive heating loads with UAΔT and cooling loads with the CLTD method.
Unit thermal resistance of a solid layer; = thickness (ft or in), = conductivity (Btu·in/(h·ft²·°F) or Btu/(h·ft·°F)). Units of are h·ft²·°F/Btu.
Add layer and film resistances in series; is the reciprocal. (still indoor air), winter / summer.
For framing and other parallel paths; = area fraction, = transmittance of path . Weight U-values, never R-values.
Design heating load through a surface, Btu/h. No solar or internal credit; in ft², in °F.
Gain from an adjacent unconditioned space at temperature to the conditioned space at (handbook §9.1.9).
Cooling load through a sunlit wall or roof, Btu/h. CLTD (°F) embeds sol-air temperature and mass time lag.
Adjusts a table value (78 °F indoor, 85 °F mean outdoor basis) to actual design temperatures; .
Overall U-factor of a cavity wall
Problem. A wall is built (outside to inside) of a 7.5 mph summer air film, face brick (), exterior sheathing (), an R-13 insulated cavity, gypsum board (), and a still indoor air film (). The handbook lists the winter outdoor film as and the indoor film as . Using the winter outdoor film, find the clear-cavity -factor and the steady-state heating load through when indoors is and outdoors is .
Thermal bridging by wood framing
Problem. The same wall has its cavity interrupted by nominal wood studs that occupy of the wall area (the cavity is the other ). The stud path replaces the R-13 cavity with of wood at ; all other layers are unchanged. Find the area-weighted assembly and compare with the clear-cavity value.
Sunlit-wall cooling load with corrected CLTD
Problem. A west-facing masonry wall has and area . The CLTD table gives at the design hour. The space is kept at ; the outdoor design dry bulb is with a daily range. Find the wall cooling load.
Quantify sensible and latent gains from occupants, lighting (use and ballast factors), and motors/appliances, then split them radiant/convective and diversify.
Unlocks with an access pass — one-time payment, no auto-renew. View passes
Size supply CFM from the room sensible load and supply-to-room ΔT using the 1.10 equation, find the leaving-air temperature, and add reheat at part load.
Unlocks with an access pass — one-time payment, no auto-renew. View passes
Compute outdoor-air sensible (1.10·CFM·Δt) and latent (4,840·CFM·ΔW) loads, find infiltration by air-change and leakage methods, and add OA load to the coil.
Unlocks with an access pass — one-time payment, no auto-renew. View passes
Compute solar gain through glazing with SHGC and irradiance, relate it to the shading coefficient and external shading, and convert to cooling load with the CLF.
Unlocks with an access pass — one-time payment, no auto-renew. View passes